BS 5839-1 or BS 5839-6? Which fire alarm standard applies to your building

  • Home
  • BS 5839-1 or BS 5839-6? Which fire alarm standard applies to your building
Pagetitleicon
Image

BS 5839-1 covers fire alarm systems in non-domestic buildings such as offices, shops, factories, warehouses, schools and care homes. BS 5839-6 covers fire alarms in homes. If you run, own or manage a commercial building, BS 5839-1 is almost always the standard your system should be designed, installed and maintained to. This guide explains what each part covers, where the line falls in buildings that mix homes and businesses, and what the Part 6 grades and categories mean if you come across them.

SAFE engineer testing a ceiling smoke detector in a shop

What is BS 5839?

BS 5839 is the British Standard for fire detection and fire alarm systems in buildings. It is split into several parts. The two that most people search for are:

  • BS 5839-1: the code of practice for the design, installation, commissioning and maintenance of fire detection and alarm systems in non-domestic premises.
  • BS 5839-6: the code of practice for fire detection and fire alarm systems in domestic premises.

Neither part is a law in itself. But the Regulatory Reform (Fire Safety) Order 2005 requires the Responsible Person for a non-domestic building to provide appropriate fire detection and warning and to keep it in efficient working order. Fire and rescue services, insurers and fire risk assessors use BS 5839-1 as the yardstick for what “appropriate” looks like.

BS 5839-1: fire alarms for non-domestic buildings

Part 1 applies to almost every building that isn’t somebody’s home. That includes offices, shops and retail units, factories and warehouses, schools and academies, leisure centres, hotels, hospitals and healthcare buildings, and residential care homes. Care homes sit under Part 1 because they are workplaces where staff care for residents, not private homes.

Part 1 sets out how a system should be designed for the building and the way it is used, which category of system is needed, and how it should be installed, commissioned, handed over and serviced. Systems are described by category:

  • Category M: manual call points only, so people raise the alarm themselves.
  • Categories L1 to L5: automatic detection designed to protect life, from L1 (detection throughout the building) to L5 (detection engineered to a specific objective).
  • Categories P1 and P2: automatic detection designed to protect property.

Your fire risk assessment should say which category your building needs. Our BS 5839-1 guide for commercial buildings goes through the categories, design, commissioning and servicing in more detail.

BS 5839-6: fire alarms for homes

Part 6 covers fire detection and alarms in domestic premises, such as houses, bungalows and individual flats. Instead of L and P categories with a control panel, it uses its own system of grades and categories, which describe how the alarms are powered and connected and which rooms are covered.

The grades describe the type of system:

  • Grade A: a system of detectors and sounders connected to a control and indicating panel, much like a small Part 1 system.
  • Grade C: detectors and sounders, or interlinked alarms, with a central control unit and a standby power supply.
  • Grade D1: mains-powered smoke and heat alarms with a built-in, tamper-proof standby battery.
  • Grade D2: mains-powered alarms with a standby battery the user can replace.
  • Grade F1 and F2: battery-only alarms, with a sealed long-life battery (F1) or a replaceable battery (F2).

The categories describe the coverage:

  • LD1: alarms in escape routes and every room where a fire could start, apart from low-risk rooms such as bathrooms.
  • LD2: alarms in escape routes and in rooms that pose a higher risk.
  • LD3: alarms in escape routes only.
  • PD1 and PD2: coverage designed to protect property.

So when you see “Grade D1, Category LD2”, that means mains-powered interlinked alarms with sealed backup batteries, fitted in the escape routes and the higher-risk rooms.

The main differences at a glance

BS 5839-1BS 5839-6
Applies toNon-domestic buildingsHomes
Typical systemControl panel, detectors, call points, sounders and beacons, often addressableInterlinked smoke and heat alarms; larger homes may have a panel system
How it is describedCategories M, L1 to L5, P1 and P2Grades A, C, D1, D2, F1, F2 and categories LD1 to LD3, PD1 and PD2
Manual call pointsYes, on escape routes and at exitsNot usually
Who is responsibleThe Responsible Person under the Fire Safety OrderThe occupier or owner of the home
ServicingA competent person at least every six months, plus weekly testsDepends on the grade, from regular user tests to periodic servicing for panel systems
Fire alarm manual call point being tested with a test key

Buildings that mix homes and businesses

This is where most of the confusion comes from. Plenty of buildings in the West Midlands have a shop, office or takeaway on the ground floor with flats above, or sit in a block with communal stairs and corridors. As a general guide:

  • The commercial part of the building, such as the shop, office or restaurant, needs a system to BS 5839-1.
  • The flats themselves fall under BS 5839-6.
  • Communal areas such as shared stairs and corridors are not part of anyone’s home, so the Fire Safety Order applies to them. Where they need a fire alarm system, which isn’t always the case in purpose-built blocks of flats, it is usually designed to BS 5839-1, although Part 6 covers some smaller shared buildings and sheltered housing schemes. Your fire risk assessment should say which applies.
  • Whether the systems are linked depends on the building and how people escape from it. Your fire risk assessment, and the fire strategy if there is one, should set out how the business and the flats are warned of a fire.

Because every mixed-use building is different, the safest route is to get the fire risk assessment right first and then have the fire alarm designed to match it. We partner with select, highly experienced fire risk assessors we know and trust, and our own experienced engineers design and install the system the assessment calls for.

What this means if you run a commercial building

  • Your fire alarm should be designed, installed and serviced to BS 5839-1, with a category that matches your fire risk assessment.
  • Smoke alarms bought for a home are not a substitute for a Part 1 system in a shop, office, factory or care home.
  • You need a weekly test from a different call point each time and a service by a competent person at least every six months. Our guide on how often fire alarms should be tested explains the checks.
  • Keep the logbook, the design, installation and commissioning certificates, and the service records. They are what a fire officer, insurer or assessor will ask to see.
  • If your system was fitted by someone else, we can take it over. Our own experienced engineers work on both open and closed protocol systems.
SAFE engineer working inside an open fire alarm control panel during a service visit

How SAFE can help

SAFE Fire & Security designs, installs and maintains fire alarm systems for commercial buildings across Birmingham, the Black Country and the wider West Midlands, from our office in Halesowen. We are BAFE SP203-1 registered for fire alarm systems, NSI approved and NICEIC registered, and our own experienced engineers carry out the work. We work on commercial premises only.

See our pages on commercial fire alarm installation and fire alarm servicing and maintenance, or read our guide to commercial fire alarm systems and the types of fire detector.

Not sure which standard your building falls under? Call us on 0333 224 0247 or book a free site survey and we’ll tell you plainly what your building needs.

Frequently asked questions

What is the difference between BS 5839-1 and BS 5839-6?

BS 5839-1 is the code of practice for fire detection and alarm systems in non-domestic buildings such as offices, shops, factories, schools and care homes. BS 5839-6 covers fire alarms in homes. Part 1 describes systems by category (M, L1 to L5, P1 and P2), while Part 6 uses grades (A, C, D1, D2, F1, F2) and categories (LD1 to LD3, PD1 and PD2).

Does BS 5839-6 apply to commercial premises?

No. BS 5839-6 is for domestic premises. Commercial and other non-domestic buildings should have a fire alarm system designed, installed and maintained to BS 5839-1, with a category that matches the fire risk assessment.

Is BS 5839-1 a legal requirement?

BS 5839-1 is not a law in itself. But the Regulatory Reform (Fire Safety) Order 2005 requires the Responsible Person to provide appropriate fire detection and warning and keep it working, and fire and rescue services, insurers and fire risk assessors use BS 5839-1 as the benchmark for what that means.

Which standard applies to a care home?

Residential care homes are non-domestic premises, so their fire alarm system should be designed, installed and maintained to BS 5839-1. Care homes usually need a high level of automatic detection, and the right category is set by the fire risk assessment.

What about a shop with flats above it?

As a general guide, the shop needs a fire alarm system to BS 5839-1 and the flats fall under BS 5839-6. Shared stairs and corridors come under the Fire Safety Order. How the systems are linked, and how everyone is warned of a fire, should be set out in the building’s fire risk assessment.

What does Grade D1 Category LD2 mean?

It is a BS 5839-6 description for homes. Grade D1 means mains-powered smoke and heat alarms with a built-in, tamper-proof standby battery. Category LD2 means alarms in the escape routes and in rooms that pose a higher fire risk.

How often should a commercial fire alarm be serviced?

Under BS 5839-1, a competent person should service a commercial fire alarm system at least every six months, and someone on site should test it weekly from a different call point each time. Keep the results in the fire alarm logbook.